Sand Profile · Randwick
Geotechnical Investigation
Loose Sand, Read For Screw Piles
Randwick · rear extension, garage and pool on screw piles
The brief. A two-level rear extension, a garage with a studio above on the rear lane, and an in-ground pool, all carried on steel screw piles. The piling design needed the depth of dense sand and of rock.
On the ground. Four rig boreholes with penetrometer tests found up to 0.8 metres of fill over loose sand, then clayey sand becoming dense from about 2.4 to 2.7 metres, to auger refusal on inferred weathered sandstone at 3.65 to 4.1 metres. At the lane end, wet sand sat above inferred rock at 3.1 metres.
The outcome. Class P under AS 2870, because the loose sand cannot carry footings at practical depths. The report set screw pile parameters area by area, with the pool, shoring, earth pressures and groundwater control for the excavations.
4 rig boreholes with penetrometer tests · Class P · Screw pile parameters by area